Brief Specifications
Measuring ParameterMonitors Over Load (As per NEMA Curve), Over Current, Under Current / Dry run, Locked current, Over voltage, Under Voltage, Phase failure
Electrical Connection3Ø - 3
Test / ResetManual / Auto reset
LED IndicationPower ON, Current and Voltage parameter
Voltage Measuring Range280V AC to 500V AC (L - L)
Motor Rated Current Measuring range280V 3A - 80A (via external MPCT)
Power Consumption40VA (max)
Output ContactControl Output 1 C/O (SPDT),
Relay Rating NO 5A@250V AC / 28VDCNC 3A@250V AC / 28VDC

Accuracy
Current Accuracy ±5% of rated current,
Voltage Accuracy ±1% of 500V,
Time Accuracy ±5% ±100msec





Functional Specifications
Over Load NEMA class 5, 10, 15, 20, 30,
Over Current Ranges For 10A CT : (Ir + 1) A to 60A,
For 40A CT : (Ir + 1) A to 240A,
For 80A CT : (Ir + 1) A to 480A,
Under Current For 10A CT : 1A to (Ir - 1)A,
For 40A CT : 5A to (Ir - 1)A,
For 80A CT : 10A to (Ir - 1)A,
Current Asymmetry [1A to Ir-1],
Locked Current / Stall Current: For 10A CT : (Ir + 1)A to 60A,
For 40A CT : (Ir + 1)A to 240A,
For 80A CT : (Ir + 1)A to 480A,
Over Voltage 280V - 500V (L - L),
Under Voltage 280V - 500V (L - L),
Voltage Asymmetry 10V to 50Vtd>



Time Setting
Power ON Delay 1sec (Fixed),
Trip Time Delay 0, 2, 4, 6, 8 & 10 sec,
(Current & Voltage parameters),
Auto reset time 15min,
(Current & Voltage parameters),
Phase Loss Instantaneous (<240ms),
Phase Reversal Instantaneous (<240ms)
Auto Restart Attempts3 (Fixed)
Restart Attempt Time Frame1 - 999 mins for current & voltage parameters
MountingDIN Rail Mount
Size71.2 x 70 x 90 (H x W x L)