Brief Specifications
Input Voltage90 - 264 VAC (127 - 370 VDC)
Input Frequency50/60 Hz
Inrush Current< 48 Amps; Measured at 264 VAC, 25°C Ambient, Cold start
Output Voltage24V & 48V
Output Power480 W
Voltage Tolerance± 1 %
Line Regulation< 1% of Vout
Load Regulation± 1 %
Turn On Time< 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load
Hold Up Time≥60ms at 230V AC & ≥15ms at 115V AC, Full load
Rise Time< 100 ms
Overload Protection> 110% of rated output current; Hiccup type; Autorecovery
Overvoltage ProtectionLatched type; Input AC power to be recycled to recover the power supply
Output Short Circuit ProtectionHiccup mode when output is shorted; Autorecovery type
Operating Temperature- 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,- 25°C to 0°C start-up is guaranteed with specification deviation
Storage Temperature- 40°C to + 85°C
CoolingNatural convection cooled
Humidity5 to 95 % RH, Non condensing
Altitude2000 m
Dimension60 x 154 x 158.55 mm (W x H x D)
Weight1050 gms
Mounting35 mm Din rail