OPS 40W Series
Product Code: OPS2x3-40-48-A-1-CU
                        - 3 x 2 x 1.16 Inches Form factor
 - 40 Watts Convection
 - Efficiencies up to 86 %
 - -40 to 70°C operating temperature, Thermal Shut-Down feature
 - Medical (BF) Safety Approvals
 - Means of Protection : 2xMOPP
 - No Load Power < 0.5W
 - Class II Option Available
 - Approved to Household, ITAV and Medical standards
 
Brief Specifications
| Input Voltage | 90 - 264 VAC (127 - 370 VDC) | 
| Input Frequency | 47 - 63 Hz | 
| Inrush Current | < 48 Amps; Measured at 264 VAC, 25°C Ambient, Cold start | 
| No Load Power | < 0.5 W | 
| Output Voltage | 5 V to 48 V | 
| Output Power | 40 W | 
| Voltage Tolerance | ± 1 % | 
| Line Regulation | < 1% of Vout | 
| Load Regulation | ± 1 % | 
| Turn On Time | < 1 sec @ 230 VAC & < 3 sec @ 115 VAC, Full load | 
| Hold Up Time | ≥60ms at 230V AC & ≥15ms at 115V AC, Full load | 
| Rise Time | < 100 ms | 
| Overload Protection | > 110% of rated output current; Hiccup type; Autorecovery | 
| Overvoltage Protection | Latched type; Input AC power to be recycled to recover the power supply | 
| Output Short Circuit Protection | Hiccup mode when output is shorted; Autorecovery type | 
| Operating Temp | - 25°C to + 70°C; De-rate linearly above 50°C from 100 % load at 50°C to 50 % load at 70°C,- 25°C to 0°C start-up is guaranteed with specification deviation | 
| Storage Temp | - 40°C to + 85°C | 
| Cooling | Natural convection cooled | 
| Humidity | 5 to 95 % RH, Non condensing | 
| Altitude | 2000 m | 
| Dimension | Overall : 3” x 2” x 1.16” (LxWxH) ; Height above PCB : 1” | 
| Weight | < 100 gms | 
| Mounting | Open Frame | 
Downloads
- Sorry, file does not exists.
 
- Sorry, file does not exists.
 
English 
                
                     
                    
                    
                