                3Ø digital Pump protection relay
Product Code: PPRD-4M-3-415V
                        - Monitors: Phase loss, Phase unbalance, Phase sequence, Overload trip current, Under / Over current and voltage in 3Ø Pumps.
- Auto / Remote test available.
- MPCT range : 10A - 80A
- Output Contact : 1 C/O SPDT relay
- Operating Range : 280 - 500V AC (L-L)
Brief Specifications
| Measuring Parameter | Monitors Over Load (As per NEMA Curve), Over Current,Dry Run/Under Current, Locked Current, Current Asymmetry, Phase Sequence, Phase Failure, Over Voltage, Under Voltage, Voltage Asymmetry | 
| Electrical Connection | 3Ø - 3 | 
| Test / Reset | Manual / Auto reset | 
| LED Indication | Power ON, Trip indication | 
| Voltage Measuring Range | 280V AC to 500V AC (L - L) | 
| Power Consumption | 40VA (max) | 
| Output Contact | Control Output 1 C/O (SPDT), Relay Rating NO 5A@250V AC / 28VDCNC 3A@250V AC / 28VDC | 
| Accuracy | Current Accuracy ±5% of rated current, Voltage Accuracy ±1% of 500V, Time Accuracy ±5% ±100msec | 
| Functional Specifications | Over Load NEMA class Curve 5, 10, 15, 20, 30, Over Current Ranges 10% - 70% of Ir (Rated Current), Under Current 20% - 80% of Ir (Rated Current), Current Asymmetry Fixed : 50% of Ir (Rated Current), Locked Current / Stall Current Fixed : 300% of Ir (Rated Current), Over Voltage Fixed (480V), Under Voltage Fixed (350V) | 
| Time Setting | Power ON Delay 1sec (Fixed), Trip Time Delay 0, 2, 4, 6, 8 & 10 sec, (Current & Voltage parameters), Auto reset time 15min, (Current & Voltage parameters), Phase Loss Instantaneous (<240ms), Phase Reversal Instantaneous (<240ms) | 
| Auto Restart Attempts | 3 (Fixed) | 
| Restart Attempt Time Frame | 60min (Fixed) for current & voltage parameters | 
| Mounting | DIN Rail Mount | 
| Size | 66.50 x 70 x 90 (H x W x L) | 
Downloads
- Sorry, file does not exists.
- Sorry, file does not exists.
Related Products
                    PPRA-4M-3-415V
                    
                            
                    
                        
                            
                                
                                
                                
                                    
                                
                            
                            
                        
                        
                            
                                
                                
                            
                        
                    
                Analog PPR for 3P-3W systems, 1 C/O (SPDT) relay, Voltage Measuring Range 280V AC to 500V AC (L - L)
$ 98.00
$ 98.00
 Out Of stock
3Ø Pump protection relay which monitors Overload (As per NEMA Curve)Over / Under current, Over / Under Voltage, Current asymmetry ,Phase loss, Phase sequence.
 English
English 
 
                 
                     
                      
                     
                     
                